Pin-Type Insulators

Low Voltage

Previous Page

 

 

 

 

 

 

 

Previous Page

 

 

 

 

 

 

 

 

 

 

 

 

Previous Page

Catalog Num. 551KG 552KG 553KG
Dimensions (in.)

Pin Hole Diameter

Recommended Pin Length

Leakage Distance

Dry Arcing Distance

 

1

4

4

2-1/4

 

1

4

5

3-3/8

 

1

5

7

4-1/2

Mechanical Values-Ultimate*

Cantilever Strength (lbs.)

 

3000

 

2500

 

2500

Electrical Values (kV)

Typical Voltage Class

Low Frequency Dry Flashover

Low Frequency Wet Flashover

Impulse Flashover, Positive

Impulse Flashover, Negative

Low Frequency Puncture

Voltage

 

4.8

35

20

50

70

 

50

 

7.5

45

25

70

85

 

70

 

11.5

55

30

90

110

 

90

Radio Influence Voltage Data

Test Voltage, RMS to Ground (kV)

Maximum RIV at 1000 kHz (kV)

 

5

50

 

5

50

 

10

50

Packing & Shipping Data

Net Weight Each (lbs.)

Packed Weight Each (lbs.)

Standard Package Qty.

 

1.28

1.37

48

 

1.50

1.57

32

 

2.03

2.30

24

 

 


Universal Clay Products | 1528 First Street | P.O. Box 438 | Sandusky, OH 44870 | Tele: 419-626-4912 | Fax: 419-626-3987