Suspension Insulators

Suspension Insulators

Previous Page

 

 

 

 

 

 

 

 

 

 

 

 

Previous Page

 

 

Catalog Num. 521 KG 523KG 524KG
Dimensions (in.)

Leakage Distance

Dry Arcing Distance

 

7

4.5

 

11-1/2

7.8

 

11-1/2

7.8

Mechanical Values (lbs.)

Combined M&E Strength

Impact Strength (inch-pounds)

Routine Proof Test Load

Time Load Test Value

Maximum Working Load

 

10,000

45

5,000

6,000

5,000

 

15,000

55

7,500

10,000

7,500

 

15,000

55

7,500

10,000

7,500

Electrical Values (kV)

Low Frequency Dry Flashover

Low Frequency Wet Flashover

Impulse Flashover, Positive

Impulse Flashover, Negative

Low Frequency Puncture Volt.

 

60

30

100

100

80

 

80

50

125

130

110

 

80

50

125

130

110

Radio Influence Voltage Data

Test Voltage, RMS to Ground (kV)

Maximum RIV at 1000 kHz (µV)

 

7.5

50

 

10

50

 

10

50

Packing & Shipping Data

Net weight Each (lbs.)

Packed Weight Each (lbs.)

Standard Package Qty.

 

5.73

6.81

12

 

11.46

14.12

6

 

11.46

14.03

6

 